- HOME > Products > Research, Development Product > Alarm Device

Use : Mosaic PNL & other monitoring devices
- Product

- This product is made of a converter, an output unit, and a repeater. The max 256 malfunction signals can be converted into communication signals. This communication module uses the bell/ buzzer/group LED lamps to notift the worker of the current status of the site.
Features
| 1. The malfunction signal entered at the site is converted into an RS-485 communication signal that is entered in a repeater and an output unit. |
|
|---|---|
| 2. The flickering time of the group lamp/bell/buzzer is simple adjusted at the repeater. |
|
| 3. Max 256 channels of alarm circuits. | - Can be expanded to one repeater, 8 converters, and 4 output units. |
| 4. Converter dip switch used. | - Can select output type for each channel- bell(heavy malfunction)/buzzer (light malfunctions). - Can select malfunction signal for each channel (8 channels) :“A" contact point (NO)/"B" contact point(NC). |
| 5. Converter first-up switch used. | - Select general sequence/First-up sequence. |
| 6. Repater used to decrease the amount of wiring. | |
| 7. Additional lamp to indicate the communication status of your converter, relay and output unit. Can check at the front of PNL. |
|
| 8. Connector used to connect the output unit to the lamp. |
Specification
| Control Power Source | DC 24V / DC48V / DC125±10% | |
|---|---|---|
| Power Consumption | Conversion | 75mA |
| Transfer | 125mA | |
| Output | 200mA | |
| Signal Duration Time | 5ms | |
| Temperature | -20~55℃ | |
| Humidity | 0~95% RH | |