본문 바로가기 네비게이션 바로가기
Yousung is leading the world to open the Smart Grid Enery Going Green
  • HOME > Products > Research, Development Product > Automatic Voltage Regulator
  • Automatic Voltage Regulator According to Load

Use : Automatic votage control of OLTC for parallel operation transformers

Automatic Voltage Regulator According to Load
- Processing Speed, Accuracy Improvement
- Parallel Operation Function(up to 8 sets of transformer)
- DVM Function
- Monitoring Function
- Event Data Record
- Tap Operation of OLTC Counting Function
- Communication Interface
Product
The product is automatic voltage regulator to operate transformer tap switching device (On Load Tap Changer, OLTC). It can control the voltage according to each load characteristics and can supporting parallel operation up to 8 sets of transformer without any additional devices and also, it can adjust the voltage effectively by bus/line voltage drop as it includes Digital Voltage Meter(DVM) function too.

Features

1. Processing Speed,
   Accuracy Improvement
- Adopt 32bit Digital Signal Processor
- Possible to measure 0.1V and 0.01A by 16Bit A/D Converter
2. Parallel Operation
   Function
- Parallel operation methods : Master/Follower and CRC method
- Possible to support parallel operation up to 8 sets of transformer
3. DVM Function - Possible to regulate voltage though the voltage of bus and feeder
   decrease rapidly
4. Monitoring Function - Event data(up to 110ea) record
5. Tap Operation of OLTC
   Counting Function
- Count and record the number of tap operation
- Possible to forecast a maintenance time for on load tap changer
6. Communication Interface - Offer communication interface with the RS-232C and RS-485 port
- Check an information of event and change setting values through HMI
   which is offered by manufacturer

Main functions

1. Control functions
- Automatic OLTC control for transformers in parallel operation
2. Metering function
- CT, PT input current(A) & voltage(V)
3. Communication function
- Front : RS232C, Rear: RS485

Specification

Control Power Source DC 125V ±20%, 60Hz, 50Hz(Option)
Rated Current AC 5A
Voltage AC 60~160V
Input Contact Current 1ea
Voltage 1ea
Digital 5ea(Volt-change 1, Volt-change 2, Parallel 1, Parallel 2, Manual)
Analog 2ea(Potential Meter, 4~20mA)
Output Contact Control 2ea('1a1b' contact×2ea)
Alarm 3ea('1a1b' contact×3ea)
Error ea(Relay fault '1a1b' contact×1ea, Parallel On '1a1b' contact×1ea,
Parallel Fault '1a1b' contact×1ea)
Communication Front RS-232C
Rear RS-485 for parallel operation
Outer Case Structure Draw out Type
Material Steel, Aluminum
Size 230×330×90(mm)