- HOME > Products > Research, Development Product > Digital Protection Relay

Use : Impact pressure meter(96P) malfunction prevention

- - Digital Protection Relay base on Real-Time Operation
- - Overcurrent Protection Function to Prevent Malfunction of 96P(50(96P))
- - Self Diagnosis Function
- - Event Data Record
- - Easy to Maintenance
- Product
- The product is an overcurrent relay to prevent malfunction of 96P relay by fault current in case fault of outside on transformer
Features
| 1. Digital Protection Relay base on Real-Time Operation |
- Adopt 32bit digital signal processor |
|---|---|
| 2. Overcurrent Protection Function to Prevent Malfunction of 96P(50(96P)) |
- Instantaneous "B" contact (point) output within 15msec which the time is faster than operation time of 96P Relay |
| 3. Self Diagnosis Function | - Setting value, Memory(ROM/RAM/Clock), Power source, A/D converter, In-output circuits |
| 4. Event Data Record | - Record of all events related to protection and control - Offered PC interface using the RS-232C port - Check an information of event and change setting values though HMI which is offered by manufacturer |
| 5. Easy to Maintenance | - Draw out type which is easy to maintenance |
Main functions
- 1. Protection metering function
- - 96P Blocking
- 2. Metering function
- - Each phase current(A)
- 3. Communication function
- - Front: RS232C, Rear: RS485
Specification
| Control Power Source | DC 125V ±20%, 60Hz | |
|---|---|---|
| Rated | Current | AC 5A |
| Input Contact | Current | 4ea (A, B, C, N-phase current) |
| Digital | 1ea (Clear) | |
| Output Contact | Control | 3EA('b' contact×3ea) |
| Alarm | 6EA( 'a' contact×1ea, 'b' contact×1ea) | |
| Communication | Front | RS-232C |
| Rear | RS-485 | |
| Outer Case | Structure | Draw Out Type |
| Material | Streel | |
| Size | 172 x 226 x 223 mm | |