Yousung is leading the world to open the Smart Grid Enery Going Green
  • HOME > Products > Research, Development Product > Digital Protection Relay
  • Over Current Relay with Reclosing(YSOC-7900R)

Use : Feeder protection KEPCO / IEC standards, two types available.

Over Current Relay with Reclosing(YSOC-7900R)
- Overcurrent Protection Function (50/51, 50N/51N)
   KEPCO and IEC standard Characteristic Curve
- Reclosing Function(79)
- Unbalance Alarm Function(UBOC)
- OLTC Blocking Function(50(OLTC))
- Monitoring and Control Function
- Self Diagnosis Function
- Fault and Event Data Record
Product
The product operates by over current which occurs during power system faults and it is added reclosing function &load unbalance detection function with 50/51 relay. It is designed to fit with protection, supervision, control & measurement in the distribution line.

Features

1. Overcurrent Protection
   Function (50/51, 50N/51N)
- Adopt characteristic curve according to KEPCO and IEC standard
2. Reclosing Function(79) - Operating up to 3 times
- After setting one time reclosing by internal manu, it can block
   instantaneous trip
- After finishing of reclosing, Instantaneous trip will return automatically
3. OLTC BLOCKING 기능
   (UBOC)
 
4. OLTC Blocking
    Function(50(OLTC))
- Send blocking signal to stop operating on load tap changer during
   reclosing(79) operates
5. Monitoring and Control
    Function
- Monitoring of contacts status in circuit breaker
- Remote control of contacts status in circuit breaker
6. Self Diagnosis Function - Setting value, Memory(ROM/RAM/Clock), Power source, A/D converter,
   In-output circuits
7. Fault and Event Data
    Record
- Event data(up to 256ea) and Fault data(up to 16ea) record
- Change setting values and analyze fault data though HMI which is offered
   by manufacturer
- Possible to change to comtrade file

Main functions

1. Protection metering function
- Overcurrent metering (50/51)
- Recloser function (79)
- Reverse overcurrent metering (46)
2. Metering function
- Each phase current (A)
3. Communication function
- Front: RS232C, Rear: RS485

Specification

Control Power Source DC 90 ~ 140V, 60Hz
Rated Current AC 5A
Input Contact Current 4ea (A, B, C, N-phase current)
Digital 5ea(CB-b, Trip Blocking, Manual Lock, 43RC, Reset)
Output Contact Control 5ea('a' contact×4ea, '1a1b' contact×1ea)
Alarm 9ea('2a' contact×8ea, '2b' contact×1ea)
Communication Front RS-232C
Rear RS-485 (Option)
Outer Case Structure Draw Out Type
Material Steel
Size 172 x 226 x 221 mm