본문 바로가기 네비게이션 바로가기
Yousung is leading the world to open the Smart Grid Enery Going Green
  • HOME > Products > Research, Development Product > Digital Protection Relay
  • DC Ground Processing Relay(DGPS-C30, C60)

Use : To protect the protection systems within a power plant/transformer station.

DC Ground Processing Relay(DGPS-C30, C60)
- Digital Protection Relay base on Real-Time Operation
- Detect Fault Signal by CT with Communication
- Measurement Method by Removing Noise Signal
- Possible to Select Fault Detection Method in Each Channel
- Possible to Extend and Select Channels
- Monitoring and Control Function by Communication Interface
Product
The product has alarm output function per each channel & fault record function in case grounding fault is occurred, as it is always monitoring the leakage current values in DC power supply line (P/N phase) at the power plant or the substation through CT with communication.

Features

1. Digital Protection Relay
   base on Real-Time
   Operation
- Adopt 32bit digital signal processor
2. Detect Fault Signal by CT
   with Communication
- Use RS-485 communication between DGPS to DCT
- Detective current range: 1~12mA, Accuracy: ±2%
3. Measurement Method by
   Removing Noise Signal
- Adopt measurement method which removes noise signal by learning
   in advance
4. Possible to Select Fault
   Detection Method in Each
   Channel
- Absolute method, Increment method
5. Possible to Extend and
   Select Channels
- Possible to select channel number from 30ea to 60ea
6. Monitoring and Control
   Function by
   Communication Interface
- Local: RS-232C port
- Remote: RS-485 port(Possible to extend DGPS up to 10ea)

Main functions

1. Protection metering functions
- Leakage current detection
2. Metering function
- Leakage current in each channel(mA)
3. Communication function
- Front : RS232C, Rear: RS485

Specification

Control Power Source DC 125V ±20%, 60Hz
Rated Voltage AC 5A
Input Contact Voltage 1ea(DC line voltage)
Digital 2ea(SCADA Clear, Spare)
Output Contact Signal Generator AC 30~65V, 27.5Hz
Alarm 4ea('a' contact×3ea, ‘1a1b’ contact×1ea)
Communication Front RS-232C
Rear RS-485×6ea
Outer Case Material Steel
Size 400×191×110(mm)