- HOME > Products > Research, Development Product > Indicator

Use : Transformer OLTC's tab indicator interconnected
- Product

- This product is a converter interconnected with a binary input tab indicator for transformer OLTC. When noise or arc causes malfunctions, this product can minimize the effects on the OLTC devices. It receives the tab information of the transformer OLTC in binary codes to display the tab location and sends an outout of binary codes to the tab indicator.
Features
| 1. In/output function | - Input : binary code (BCD) - Out : binary code (BCD) |
|---|---|
| 2. DRY contact points used. Highly compatible with other products. |
사양
| Control Power Source | AC 110~240V | |
|---|---|---|
| Frequency | 60Hz | |
| Capacity of outer Contact | Instance | AC 250V 10A, DC 30V 10A |
| Time Delay | AC 250V 5A, DC 30V 5A | |
| Outer Case | Structure | Draw Type |
| Material | Plastic | |
| Insulation Resistance | Over 10MΩ | |
| Dielectric Withstand | 2kV/1minute | |
| Noise Withstand | ±2kV R, S phase, pulse 1μs | |
| Vibration | Vibration withstand | 10~55Hz , 0.75mm X.Y,Z 2hour |
| Mal-operation | 10~55Hz , 0.5mm X.Y,Z 1hour | |
| Shock | Shock withstand | 100m/s2 (10G) X,Y,Z 3times |
| Mal-operation | 300m/s2 (30G) X,Y,Z 3times | |
| life expectancy of the relay | Mechanical | 20000000 ps Min |
| Electrical | Over 100000 이상 ps Min | |
| Temperature | -10~55℃ | |
| Humidity | 35~85% RH | |