- HOME > Products > Research, Development Product > Smart Protection Relay


- - Multifunctional Protection and Measurement
- - Monitoring and Control Function
- - Interlock Logic Function based on PLC
- - Self Diagnosis Function
- - Event and Fault Record Function
- - IEC61850 Communication Protocol
(KEMA Certication : NO. 74101864 – MOC/INC 12-01488)
- Product
- The Product is an Intelligent Electronic Device(IED) which is designed to carry out various functions such as protection, monitoring, control, measurement, interlock functions for 25.8kV GIS in digital substation and the IED uses for protecting main transformer’s secondary Main feeder/Distribution line, Sh.C, S.Tr/Bus Tie, Bus section/PT bay.
Features
| 1. Protection Function | - OCR(50/51N), Reclosing(79), OVR(59), UVR(27), NGR(59GA, 59GT), UBOC |
|---|---|
| 2. Measurement Function | - Current(A), Voltage(V), Apparent Power(AV), Active Power(P), Reactive Power(Q), Power Factor(PF), Frequency(F) |
| 3. Monitoring and Control Function |
- Monitoring contacts of CB/DS/ES - Remotely control contacts of CB/DS/ES |
| 4. Interlock Logic Function based on PLC |
- Replace conventional circuits with configuration of various Interlock logics base on programmable Logic Controller |
| 5. Self Diagnisis Function | - Setting value, Memory(ROM/ RAM/ Clock), Power source, A/D converter, In-output circuits |
| 6. Event and Fault Record Function |
- Recoard all event related to protection and control - Change setting values and analyze fault data though HMI which is offered by manufacturer - Possible to change comtrade file |
| 7. IEC 61850 Communication Protocol |
- Offer MMS, Goose, Report signals - Setting Group Support - Acquire the reliability through communication doubling - Improve the interoperability between third * party IEDs - Obtain the IEC 61850 certificate of Level A1 by KEMA (No.74101864-MOC.INC 12-01488) - Front USB port(for PC MMI), Rear Optic * port(for IEC 61850 Communication) |
Specification
| Control Power Source | DC 120V±20% | |
|---|---|---|
| Power Consumption | Under 30W at normal time, Under 50W during operation | |
| Rated | Current | 110/ V, 190/ V, 190/3V |
| Current | AC 5A | |
| Input Contact | Current / Voltage | 4CT, 4PT or 8PT |
| Digital | 28EA | |
| Analog | 5EA(4~20mA x 5ea) | |
| Output Contact | Control | 14EA(‘a’Contact x 14ea) |
| Alarm | 2EA(‘c’Contact x 2ea) | |
| Communication | Front | USB port for HMI |
| Rear | Optic port(ST type)×4EA(IEC 61850 : 2EA, OPTION : 2EA) LAN PORT × 1EA (for Tester) |
|
| Case | Material | Steel |
| Size | 304 × 275 × 259(mm) | |


V, 190/