본문 바로가기 네비게이션 바로가기
Yousung is leading the world to open the Smart Grid Enery Going Green
  • HOME > Products > Research, Development Product > Smart Protection Relay
  • Smart Multifunctional IED
Smart Multifunctional IED
- Multifunctional Protection and Measurement
- Monitoring and Control Function
- Interlock Logic Function based on PLC
- Self Diagnosis Function
- Event and Fault Record Function
- IEC61850 Communication Protocol
   (KEMA Certication : NO. 74101864 – MOC/INC 12-01488)
Product
The Product is an Intelligent Electronic Device(IED) which is designed to carry out various functions such as protection, monitoring, control, measurement, interlock functions for 25.8kV GIS in digital substation and the IED uses for protecting main transformer’s secondary Main feeder/Distribution line, Sh.C, S.Tr/Bus Tie, Bus section/PT bay.

Features

1. Protection Function - OCR(50/51N), Reclosing(79), OVR(59), UVR(27), NGR(59GA, 59GT), UBOC
2. Measurement Function - Current(A), Voltage(V), Apparent Power(AV), Active Power(P), Reactive
   Power(Q), Power Factor(PF), Frequency(F)
3. Monitoring and Control
   Function
- Monitoring contacts of CB/DS/ES
- Remotely control contacts of CB/DS/ES
4. Interlock Logic Function
   based on PLC
- Replace conventional circuits with configuration of various Interlock logics
   base on programmable Logic Controller
5. Self Diagnisis Function - Setting value, Memory(ROM/ RAM/ Clock), Power source, A/D converter,
   In-output circuits
6. Event and Fault Record
   Function
- Recoard all event related to protection and control
- Change setting values and analyze fault data though HMI which is offered
   by manufacturer
- Possible to change comtrade file
7. IEC 61850 Communication
   Protocol
- Offer MMS, Goose, Report signals
- Setting Group Support
- Acquire the reliability through communication doubling
- Improve the interoperability between third
   * party IEDs
- Obtain the IEC 61850 certificate of Level A1 by KEMA
   (No.74101864-MOC.INC 12-01488)
- Front USB port(for PC MMI), Rear Optic
   * port(for IEC 61850 Communication)

Specification

Control Power Source DC 120V±20%
Power Consumption Under 30W at normal time, Under 50W during operation
Rated Current 110/V, 190/V, 190/3V
Current AC 5A
Input Contact Current / Voltage 4CT, 4PT or 8PT
Digital 28EA
Analog 5EA(4~20mA x 5ea)
Output Contact Control 14EA(‘a’Contact x 14ea)
Alarm 2EA(‘c’Contact x 2ea)
Communication Front USB port for HMI
Rear Optic port(ST type)×4EA(IEC 61850 : 2EA, OPTION : 2EA)
LAN PORT × 1EA (for Tester)
Case Material Steel
Size 304 × 275 × 259(mm)